Add To Cart
share
Sick MM12-60A-N-ZW0 Overview
Magnetic proximity sensor MM12-60A-N-ZW0 NAMUR Sn 60mm, axial, 2m cable
Sick MM12-60A-N-ZW0 Description
- Detection of magnets
- Operating distances up to 60 mm or more based on the magnet strength
- NAMUR as per EN 60 947-5-6
- High switching frequency
- Rugged nickel-plated brass housing with fine thread M12 x 1 mm
- IP 67 enclosure rating
- EC-type test certificate Ex II 2G EEx ib IIC T6 TV 99 ATEX 1398
- Cylindrical design
- NAMUR design ensures safe operation in highly explosive areas
- Non-contact operation ensures resistance to dirt, dust and vibration, increasing sensor life and reducing maintenance costs
- Large operating distances ensure reliable switching, even with target position tolerances
- Non-contact, universal detection through several substances, including plastic containers and pipes and protective PTFE walls
Your benefits
| Features | |
| Sensing range Sn: | 60 mm |
| Switching frequency: | 5,000 Hz |
| Connection type: | Cable, 2-wire, 2 m 1) |
| Switching output: | NAMUR |
| Electrical wiring: | NAMUR |
| Enclosure rating: | IP 67 2) |
| 1) Do not bend below 0 C 2) According to EN60529 | |
| Mechanics/electronics | |
| Design: | cylindrical |
| Thread size: | M12 |
| Supply voltage: | 5 V DC ... 25 V DC |
| Residual ripple: | ≤ 5 % 1) |
| Hysteresis: | 1 % ... 10 % |
| Repeatability: | ≤ 1 % 2) |
| Temperature drift (of sr):: | 10 % |
| EMC: | According to EN 60947-5-2 |
| Max. tightening torque: | ≤ 7 Nm |
| Reverse polarity protection: | ![]() |
| Short-circuit protection: | ![]() |
| Housing material: | Metal, Nickel-plated brass |
| Time delay before availability: | ≤ 2 ms |
| Ambient temperature, operation: | -25 C ... 75 C |
| Shock/vibration stress: | 30 g, 11 ms/10 ... 55 Hz, 1 mm |
| Cable material: | PVC |
| Power consumption, attenuated: | ≥ 2.5 mA |
| Power consumption, unattenuated: | ≤ 1 mA |
| Cable resistance: | ≤ 50 Ω |
| EC type approval certificate: | TV 99 ATEX 1398 |
| Ex marking (ATEX): | EX II 2G Ex ia IIC T6 Ta: -20 C ... 70 C |
| Hazardous area category: | 2G |
| Input voltage Ui max: | 16 V 3) |
| Input power Pimax.: | 100 mW 4) |
| Input current Ii max: | 30 mA 5) |
| Internal capacitance Ci max.: | 15 nF 6) |
| Internalinductance Li max.: | 35 H 7) |
| Nominal voltage: | 8.2 V DC |
| Conductor cross-section: | 0.34 mm2 |
| 1) Of VS 2) Von Sr (VS und Ta constant) 3) 4) 5) 6) 7) For connection to a sperately certified intrinsically safe circuit only | |
Contact Us